Reference

Wastewater operator math formulas

A plain reference written from scratch. Formulas themselves aren’t copyrightable — these explanations and examples are our own. We don’t reproduce any official formula sheet.

Measuring & Conversions

Units, areas and volumes — the groundwork every other calculation stands on.

Flow-rate conversions

1 MGD = 694.4 gpm = 1.547 cfs

Operators move between million gallons per day, gallons per minute and cubic feet per second constantly. One MGD is a million gallons spread over 1,440 minutes, which is 694.4 gpm; dividing by 7.48 gal/ft³ and 86,400 s/day gives about 1.547 cfs.

Tank area & volume

Volume (gal) = 0.785 × D² × depth × 7.48

A round tank’s cross-section is 0.785 × D² (that is π/4 × diameter squared). Multiply by the water depth for cubic feet, then by 7.48 gallons per cubic foot for gallons.

Percent removal

% removal = (in − out) ÷ in × 100

Removal efficiency compares what came in to what left: subtract the effluent concentration from the influent, divide by the influent, and multiply by 100. A common slip is dividing by the effluent instead of the influent.

Hydraulics & Pumping

Flow, velocity, detention time and loading rates through pipes, channels and tanks.

Detention time

Detention time = Volume ÷ Flow

Detention time is how long water stays in a tank: its volume divided by the flow through it. Keep the units consistent — gallons over gallons-per-hour gives hours.

Velocity in a pipe

Velocity = Flow ÷ Area (Q = A × V)

For a full pipe, velocity equals the flow rate divided by the cross-sectional area. Convert the diameter to feet first, and convert the flow to cubic feet per second so the units cancel to feet per second.

Surface overflow rate

SOR = Flow (gpd) ÷ Surface area (ft²)

The surface overflow rate of a clarifier is the daily flow spread over its surface area, in gallons per day per square foot. Use the surface area (0.785 × D²), not the volume.

Chemistry & Dosage

The pounds formula, process-control ratios and disinfection math.

BOD & solids loading

lbs/day = concentration (mg/L) × flow (MGD) × 8.34

The pounds formula converts a concentration and a flow into a daily mass. The 8.34 is the weight of a gallon of water in pounds. Forgetting the 8.34 is the most common operator-math mistake.

Chemical feed rate

lbs/day = dose (mg/L) × flow (MGD) × 8.34

The same pounds formula sizes a chemical feeder: how many pounds per day of chlorine, alum or lime are needed to hit a target dose at the current flow.

Dosage from feed rate

dose (mg/L) = lbs/day ÷ (flow (MGD) × 8.34)

Run the pounds formula backwards to find the dosage a known feed rate actually delivers at a given flow.

Food-to-microorganism (F/M)

F/M = BOD applied (lb/day) ÷ MLVSS under aeration (lb)

The F/M ratio compares the food entering the aeration basin to the mass of bugs available to eat it. Because both sides use the 8.34 factor, it cancels and the ratio is (BOD × flow) ÷ (MLVSS × volume).

MCRT / sludge age

MCRT (days) = solids in system (lb) ÷ solids leaving (lb/day)

Mean cell residence time — also called solids retention time or sludge age — is the pounds of solids held in the system divided by the pounds leaving it each day through wasting and the effluent.

Sludge volume index (SVI)

SVI = settled volume (mL/L) × 1000 ÷ MLSS (mg/L)

SVI tells you how well sludge settles: the 30-minute settled volume times 1,000, divided by the MLSS. Low numbers settle well; high numbers warn of bulking.

Chlorine demand

Chlorine demand = dose − residual

Chlorine demand is simply the chlorine consumed: the dose applied minus the residual measured after the contact time.

Practice every formula with unlimited problems →